General
Current Probes:
- 120 A Current Clamps (CC), Class 0.2 or 0.5
- 12 A Direct, Class 0.05 or 0.1
- 1000 A Current Clamps, Class 0.2
- 3000 A Flexible Probes, Class 1
- 2000 A High Voltage Current Probe, Class 2
Test Types:
- Analysis of the Site – on the Primary or the Secondary of the Current Transformer (CT);
- Meter Error Test – on Primary or Sec. Side;
- Current Transformer Test – CT Ratio Error;
- Burden Test – of CT or Voltage Transformer;
- Meter Register Test;
- Maximum Demand Test.
Energy Types: Wh, varh, VAh
Circuit Types: 4W Wye, 3W Delta, 2W Single
Pulses Pickup: Universal Scanning Head with 3D Support or Manual Button or Functional Button.
Memory: Max. 1000 Files saved in Flash Memory; A File contains all the Tests performed on one Site.
PEWM Software, MySQL Data Base, Excel Report.
ADVANTAGES:
- Large 7” LCD Display with high brightness;
- The Parameters for each Test are on the same screen and can easily be changed;
- Choose the Meter Type – a predefined List;
- Automatic calculation of Number of Pulses for Meter Error Tests, depending on the pre-set “Test Duration” in seconds;
- Statistical Measurements (Max. 5 repeats);
- Calculation of Average Meter Error and Standard Deviation;
- Automatic Test of all three CTs, without moving the Primary & Secondary Probes;
- The On-Board Consultant issues Warning Messages in Analysis, Error and CT Tests;
- Easy Save of all performed Tests in one File, plus all Parameters, Date/Time, Meter ID;
- View all Tests in Saved Files on the Screen;
- Transfer Saved Files to a PC via USB Type C;
- Print Test Results on a Thermal Printer;
- A broken Clamp can easily be replaced and semi-auto calibrated by the Customer.